Suitable for aerial installation and for public power distribution networks
Suitable for aerial installation and for public power distribution networks
SANS 1713--- Electric cables -Medium voltage aerial bundled conductors for voltages from 3,8/6,6 kV to 19/33 kV
6.6kV-22kV
Conductor: Aluminum, circular stranded and compacted.
Conductor Screening: Extruded thermosetting semi-conductor layer.
Insulation: XLPE thermosetting material.
Insulation Screening:
Semi conducting screen: Extruded thermosetting semi-conducting layer, applied under a swellable semi-conducting tape for watertightness.
Metal screen: Plain soft copper wire and / or copper tape applied helically, or aluminum tape applied longitudinally bonded to the outer PE sheath.
Outer sheath: Extruded black PE sheath, or PVC upon specific customer requirements.
Steel Messenger: 50 or 70 mm² galvanized steel stranded wires, covered with black PE, or PVC upon specific customer requirements.
We produce quality cables by using high-end material:
Rich experience team knowing what's your demand:
Plant with good facilities and capacity to guarantee on-time delivery:
PHASE CORE | ||||||||
Conductor Size | mm² nom | 35 | 50 | 70 | 95 | 120 | 150 | 185 |
Conductor Diameter | mm app. | 7.15 | 8.25 | 9.95 | 11.80 | 13.10 | 14.80 | 15.95 |
Insulation Diameter | mm app. | 15.4 | 16.5 | 18.2 | 20.1 | 21.4 | 22.7 | 24.2 |
Core Sheath Diameter | mm app. | 20.5 | 21.6 | 23.5 | 25.5 | 26.8 | 28.1 | 29.9 |
SUPPORT CORE | ||||||||
Conductor Size | mm² nom | 50 | 50 | 50 | 50 | 70 | 70 | 70 |
Conductor Diameter | mm app. | 9.00 | 9.00 | 9.00 | 9.00 | 10.80 | 10.80 | 10.80 |
Insulation Diameter | mm app. | 11.5 | 11.5 | 11.5 | 11.5 | 13.3 | 13.3 | 13.3 |
Maximum Tensile Strength and Pulling Force of Catenary | kN | 26 | 26 | 26 | 26 | 37 | 37 | 37 |