Single core 90℃ solid conductor unsheathed cable for internal wiring .
Single core 90℃ solid conductor unsheathed cable for internal wiring .
60227 IEC 07 BV Solid Indoor Copper Building Wire is suitable for Building Wire, house wiring, used for indoor wiring, piping and other fixed laying in high temperature environment.
Rated Voltage (Uo/U):300/500V
Conductor temperature:Maximum conductor temperature in normal use: 90ºC
Installation temperature:Ambient temperature under installation shall not be below 0ºC
Minimum bending radius:
The bending radius of cable: (D-Diameter of cable)
D≤25mm------------------≥4D
D>25mm------------------≥6D
Conductor:Number of conductors:1
The conductors shall comply with the requirement given in IEC 60228 for class 1 or 2.
– class 1 for solid conductors;
– class 2 for stranded conductors.
Insulation: PVC(Polyvinyl Chloride) Type PVC/C according to IEC
Color:Yellow / green, red, yellow, blue, white, black, green, brown, orange, purple, gray etc.
60227 IEC 07 Standard
Nominal cross-sectional area of conductor mm² | Class of conductor | Nominal insulation thickness mm | Mean overall diameter Max mm | Approx, weight of cable kg/km | Max. D. C. resistance of copper conductor (20℃) Ω/km | Min. insulation resistance (90℃ Ω/km) | |
Plain | Metal-coated | ||||||
0.5 | 1 | 0.6 | 2.3 | 8 | 36 | 36.7 | 0.015 |
0.8 | 1 | 0.6 | 2.5 | 10 | 24.5 | 24.8 | 0.013 |
1 | 1 | 0.6 | 2.7 | 13 | 18.1 | 18.2 | 0.012 |
1.5 | 1 | 0.7 | 3.2 | 19 | 12.1 | 12.2 | 0.011 |
2.5 | 1 | 0.8 | 3.9 | 30 | 7.41 | 7.6 | 0.009 |