AS/NZS standard 12.7-22kV-XLPE Insulated MV Power Cable

AS/NZS standard 12.7-22kV-XLPE Insulated MV Power Cable

Specifications:

    Electricity distribution or sub-transmission networks cable typically used as primary supply to Commercial, Industrial and urban residential networks. Suitable for high fault level systems rated up to 10kA/1sec. Higher fault current rated constructions are available on request.

    Custom designed Medium Voltage cables
    For efficiency and longevity, every MV cable should be tailored to the installation but there are times when a truly bespoke cable is needed. Our MV cable experts can work with you to design a solution that matches your requirements. Most commonly, customisations affect the area size of the metallic screen, which can be adjusted to change the short circuit capacity and earthing provisions.

    In every case, the technical data is provided to demonstrate suitability and the specification honed for manufacture. All customised solutions are subject to enhanced testing in our MV Cable Testing Facility.

    Contact the team to speak to one of our specialists.

Quick Detail

Parameter Table

Application :

LSZH MV cables also include PVC single-core AWA armored cables and XLPE multi-core SWA armored cables.
This design is commonly used for auxiliary power cables in power grids and various environments. The included armor means that the cable can be buried directly into the ground to prevent accidental shock and damage.
LSZH cables are different from PVC cables and cables made of other compounds.
When a cable catches fire, it can produce large amounts of dense black smoke and toxic gases. However, because LSZH cable is made of a thermoplastic material, it produces only small amounts of smoke and toxic gases, and it contains no acidic gases.
It makes it easier for people to escape from a fire or hazardous area. Therefore, they are often installed indoors, such as in public areas, other hazardous areas, or poorly ventilated environments.

Temperature range:

Minimum installation temperature: 0°C
Maximum operating temperature: +90°C
Minimum operating temperature: -25 °C
Minimum bending radius
Installed cables: 12D (PVC only) 15D (HDPE)
During installation: 18D (PVC only) 25D (HDPE)
Resistance to Chemical exposure: Accidental
Mechanical impact: Light (PVC only) Heavy (HDPE)
Water exposure: XLPE – Spray EPR – Immersion/Temporary coverage
Solar radiation and weather exposure: Suitable for direct exposure.

Construction:

Manufactured and Type Tested AS/NZS 1429.1, IEC: 60502-2 and other applicable standards
Formation – 1 core, 3 core
Conductor – Cu or AL, Stranded Circular, Stranded Compact Circular, Milliken Segmented
Insulation – XLPE or TR-XLPE or EPR
Metallic screen or sheath – Copper Wire Screen (CWS), Copper Tape Screen (CTS), Corrugated Aluminium sheath (CAS), Corrugated Copper sheath (CCU), Corrugated Stainless Steel (CSS), Aluminium poly laminated (APL), Copper Poly Laminated (CPL), Aldrey wire screen (AWS)
Armour – Aluminium Wire Armoured (AWA), Steel Wire Armoured (SWA), Stainless Steel Wire Armoured (SSWA)
Termite Protection – Polyamide Nylon Jacket, Double brass tape (DBT), Cypermethrin
Black 5V-90 polyvinyl chloride (PVC) – standard
Orange 5V-90 PVC inner plus black high density
Low smoke zero halogen (LSOH) – alternative

Custom designed Medium Voltage cables:

For efficiency and longevity, every MV cable should be tailored to the installation but there are times when a truly bespoke cable is needed. Our MV cable experts can work with you to design a solution that matches your requirements. Most commonly, customisations affect the area size of the metallic screen, which can be adjusted to change the short circuit capacity and earthing provisions.
In every case, the technical data is provided to demonstrate suitability and the specification honed for manufacture. All customised solutions are subject to enhanced testing in our MV Cable Testing Facility.

12.7/22kV-Power cable

Cores x Nominal Area Conductor diameter (Approx.) Nominal Insulation Thickness Approx. CWS area on each core Nominal Thickness of PVC Sheath Overall Cable diameter (+/- 3.0) Short Circuit rating of Conductor/ CWS Cable Weight (Approx.) Max. Conductor DC Resistance at 20 °C
No. x mm2 mm mm mm2 mm mm kA for 1sec kg/km (Ω/km)
1C x 35 7.0 5.5 24 1.8 27.5 5 / 3 1200 0.524
1C x 50 8.1 5.5 24 1.8 28.6 7.2 / 3 1367 0.387
1C x 70 9.7 5.5 79 1.9 32.1 10 / 10 2130 0.268
1C x 95 11.4 5.5 79 2.0 33.8 13.6 / 10 2421 0.193
1C x 120 12.8 5.5 79 2.0 35.2 17.2 / 10 2687 0.153
1C x 150 14.2 5.5 79 2.1 36.6 21.5 / 10 3018 0.124
1C x 185 16.1 5.5 79 2.1 38.3 26.5 / 10 3395 0.0991
1C x 240 18.5 5.5 79 2.2 40.9 34.3 / 10 3979 0.0754
1C x 300 20.6 5.5 79 2.3 43.2 42.9 / 10 4599 0.0601
1C x 400 23.6 5.5 79 2.4 46.6 57.2 / 10 5613 0.047
1C x 500 26.6 5.5 79 2.5 49.8 71.5 / 10 6621 0.0366
1C x 630 30.2 5.5 79 2.6 53.6 90.1 / 10 7918 0.0283