IEC 60502 Standard MV ABC Aerial Bundled Cable

IEC 60502 Standard MV ABC Aerial Bundled Cable

Specifications:

    IEC 60502-2—-Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1.2 kV) up to 30 kV (Um = 36 kV) – Part 2: Cables for rated voltages from 6 kV (Um = 7.2 kV) up to 30 kV (Um = 36 kV)

Quick Detail

Parameter Table

Application:

Medium Voltage aerial bundled cables are mainly used for secondary overhead lines on poles or as feeders to residential premises.

as
df
sdf

Standard:

IEC 60502-2---- Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1.2 kV) up to 30 kV (Um = 36 kV) - Part 2: Cables for rated voltages from 6 kV (Um = 7.2 kV) up to 30 kV (Um = 36 kV)

Voltage:

6.35/11kV, 19/33kV

Construction :

Phase Conductor: Class 2 Circular compacted stranded aluminum
Conductor Screen: Extruded semi-conductive layer
Insulation: XLPE (Cross-linked polyethylene)
Insulation Screen: Extruded semi-conductive layer
Metallic Screen: Copper wire screen or copper tape screen
Separator: Semi-conductive swellable tape
Outer Sheath: HDPE (High Density polyethylene)
Support Conductor: Galvanized steel wires

COLOR:

Insulated core: Red, Yellow & Blue core marking tape
Outed sheath: Black

Characteristics:

Operating Temperature: 90°C XLPE
Temperature Range: -20°C PE sheath
Short Circuit Temperature( 5 seconds maximum duration ): 250°C XLPE
Bending Radius: 15 x overall diameter

Why Choose Us?

We produce quality cables by using high-end material:

Why Choose Us (2)
Why Choose Us (3)
Why Choose Us (1)
Why Choose Us (5)
Why Choose Us (4)
Why Choose Us (6)

Rich experience team knowing what's your demand:

1212

Plant with good facilities and capacity to guarantee on-time delivery:

1213

IEC 60502 6.35/11 kV ABC for Overhead Distribution Lines

Number of Cores x Nominal Cross Section Phase Conductor Messenger Suspension Unit Continuous Current Rating at 300°C Ambient Temp.
Stranding Nominal Sectional Area Maximum Conductor Resistance Stranding Nominal Sectional Area Breaking Load
No.×mm² No.×mm mm² Ω/Km No.×mm mm² kN A
3X50 + 1X25 19/1.78 50 0.641 7/3.0 50 60 116
3X70 + 1X50 19/.14 70 0.443 7/3.15 50 62 210
3X95+ 1X50 19/2.52 95 0.32 7/3.0 50 60 173
3X185+1X120 37/2.52 185 0.164 7/4.67 120 150 259
3X150 +1X50 37/2.25 150 0.206 7/3.15 50 62 365
3X240 +1X50 61/2.25 240 0.125 7/3.15 50 62 500

IEC 60502 19/33 kV ABC for Overhead Distribution Lines

Number of Cores x Nominal Cross Section Phase Conductor Messenger Suspension Unit Continuous current rating at 300°C ambient temp
Stranding Nominal Sectional Area Maximum Conductor Resistance Stranding Nominal Sectional Area Breaking Load
No.×mm² No.×mm mm² Ω/Km No.×mm mm² kN A
3X50 + 1X50 19/1.78 50 0.641 7/3.0 50 60 165
3X150+ 1X50 37/2.25 150 0.206 7/3.0 50 60 315
3X185+1X70 37/2.52 185 0.164 7/3.57 70 91 355
3X70 +1X50 19/2.14 7 0.443 7/3.15 50 62 250
3X150 +1X50 37/2.25 150 0.206 7/3.15 50 62 370