Medium Voltage aerial bundled cables are mainly used for secondary overhead lines on poles or as feeders to residential premises.
Medium Voltage aerial bundled cables are mainly used for secondary overhead lines on poles or as feeders to residential premises.
IEC 60502-2---- Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1.2 kV) up to 30 kV (Um = 36 kV) - Part 2: Cables for rated voltages from 6 kV (Um = 7.2 kV) up to 30 kV (Um = 36 kV)
6.35/11kV, 19/33kV
Phase Conductor: Class 2 Circular compacted stranded aluminum
Conductor Screen: Extruded semi-conductive layer
Insulation: XLPE (Cross-linked polyethylene)
Insulation Screen: Extruded semi-conductive layer
Metallic Screen: Copper wire screen or copper tape screen
Separator: Semi-conductive swellable tape
Outer Sheath: HDPE (High Density polyethylene)
Support Conductor: Galvanized steel wires
Insulated core: Red, Yellow & Blue core marking tape
Outed sheath: Black
Operating Temperature: 90°C XLPE
Temperature Range: -20°C PE sheath
Short Circuit Temperature( 5 seconds maximum duration ): 250°C XLPE
Bending Radius: 15 x overall diameter
We produce quality cables by using high-end material:
Rich experience team knowing what's your demand:
Plant with good facilities and capacity to guarantee on-time delivery:
Number of Cores x Nominal Cross Section | Phase Conductor | Messenger Suspension Unit | Continuous Current Rating at 300°C Ambient Temp. | ||||
Stranding | Nominal Sectional Area | Maximum Conductor Resistance | Stranding | Nominal Sectional Area | Breaking Load | ||
No.×mm² | No.×mm | mm² | Ω/Km | No.×mm | mm² | kN | A |
3X50 + 1X25 | 19/1.78 | 50 | 0.641 | 7/3.0 | 50 | 60 | 116 |
3X70 + 1X50 | 19/.14 | 70 | 0.443 | 7/3.15 | 50 | 62 | 210 |
3X95+ 1X50 | 19/2.52 | 95 | 0.32 | 7/3.0 | 50 | 60 | 173 |
3X185+1X120 | 37/2.52 | 185 | 0.164 | 7/4.67 | 120 | 150 | 259 |
3X150 +1X50 | 37/2.25 | 150 | 0.206 | 7/3.15 | 50 | 62 | 365 |
3X240 +1X50 | 61/2.25 | 240 | 0.125 | 7/3.15 | 50 | 62 | 500 |
Number of Cores x Nominal Cross Section | Phase Conductor | Messenger Suspension Unit | Continuous current rating at 300°C ambient temp | ||||
Stranding | Nominal Sectional Area | Maximum Conductor Resistance | Stranding | Nominal Sectional Area | Breaking Load | ||
No.×mm² | No.×mm | mm² | Ω/Km | No.×mm | mm² | kN | A |
3X50 + 1X50 | 19/1.78 | 50 | 0.641 | 7/3.0 | 50 | 60 | 165 |
3X150+ 1X50 | 37/2.25 | 150 | 0.206 | 7/3.0 | 50 | 60 | 315 |
3X185+1X70 | 37/2.52 | 185 | 0.164 | 7/3.57 | 70 | 91 | 355 |
3X70 +1X50 | 19/2.14 | 7 | 0.443 | 7/3.15 | 50 | 62 | 250 |
3X150 +1X50 | 37/2.25 | 150 | 0.206 | 7/3.15 | 50 | 62 | 370 |